Siemens Pacemaker UM344-2 Manual do Utilizador Página 183

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 183
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 182
USER’S MANUAL ADDENDUM
UMA344-2-2
Issue: 1
March 1997
Ex N INSTALLATION CONDITION
INVOLVED USER’S MANUAL
UM344-2, Issue 1, XTC™ Transmitters, Series 344 Temperature Transmitters, User’s Manual
ADDITIONAL MATERIAL
The voltage at the loop terminals of a Model 344 installed in an area requiring an Ex N rating must be prevented from
exceeding 42 Vdc. This can be accomplished by:
A double wound mains transformer to BS3535 or equivalent
An adequately rated zener diode
An adequately rated semiconductor voltage regulator
Powering the loop from a battery
Vista de página 182
1 2 ... 178 179 180 181 182 183

Comentários a estes Manuais

Sem comentários