Siemens Simatic M7-400 Manual do Utilizador Página 359

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 638
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 358
Analog Modules
5-143
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Technical Specifications of the SM 432; AO 8 x 13 Bit
Programming package
Associated programming
package
As of STEP 7 V 2.0
Dimensions and Weight
Dimensions W H D
(in millimeters)
25 290 210
Weight Approx. 650 g
Data for Specific Module
Number of outputs 8
Length of cable
Shielded Max. 200 m
Voltages, Currents, Potentials
Supply voltage of the
electronics L+
24 VDC
Rated load voltage L+ 24 VDC
Reverse polarity protection Yes
Isolation
Between channels and
backplane bus
Between the channels
Between channels and
load voltage L+
Yes
No
Yes
Permitted potential difference
Between the outputs (E
CM
)
Between S– and M
ANA
(U
CM
)
Between M
ANA
and
M
internal
(U
ISO
)
3 VDC
3 VDC
75 VDC/60 VAC
Insulation tested
Between bus and L+/M
Between bus and analog
section
Between bus and chassis
ground
Between analog section
and L+/M
Between analog section
and chassis ground
Between L+/M and chassis
ground
2120 VDC
2120 VDC
500 VDC
707 VDC
2120 VDC
2120 VDC
Current consumption
From the backplane bus Max. 150 mA
Power supply and load
voltage L+ (with rated load)
Max. 400 mA
Power supply and load
voltage L+ (no load)
Max. 200 mA
Power dissipation of the
module
Typ. max. 9 W
Analog Value Generation
Resolution including sign 13 bits
Conversion time (per channel)
In the ranges 1 V to 5 V
and 4 mA to 20 mA
420 s
In all ranges 300 s
Basic response time of module
(all channels enabled)
In the ranges 1 V to 5 V
and 4 mA to 20 mA
3.36 ms
In all the other ranges 2.4 ms
Settling time
For resistive load
For capacitive load
For inductive load
0.1 ms
3.5 ms
0.5 ms
Suppression of Interference, Limits of Error
Interference voltage suppression for f = n (f1 " 1%),
(f1 = interference frequency) n= 1.2 ...
Common-mode
interference
(U
CM
< AC 3 V
ss
/50 Hz)
>60 dB
Crosstalk between the outputs
> 40 dB
Operational limit (in the entire temperature range, with
reference to the output range)
Voltage outputs
" 10 V
0 V to 10 V
1 V to 5 V
" 0.5 %
" 0.5 %
" 0.5 %
Current outputs
" 20 mA
4 mV to 20 mV
" 1%
" 1%
Basic error (operational limit at 25 °C, referred to the
output range)
Voltage outputs
" 10 V
0 V to 10 V
1 V to 5 V
" 0.5%
" 0.5%
" 0.5%
Current outputs
" 20 mA
0 mA to 20 mA
" 0.5%
" 0.5%
Temperature error (with
reference to the output range)
" 0.02% K
Linearity error (with reference
to the output range)
" 0.05%
Vista de página 358