Analog Modules
5-125
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Technical Specifications of the SM 431; AI 8 RTD 16 Bit
Dimensions and Weight
Dimensions W H D
(in millimeters)
25 290 210
Weight Approx. 650 g
Data for Specific Module
Number of inputs
• For resistance-type sensor
8
4
Length of cable
• Shielded Max. 200 m
Voltages, Currents, Potentials
Constant current for
resistance-type sensor
Max. 1 mA
Isolation
• Between channels and
backplane bus
Yes
Permitted potential difference
• Between M
ANA
and
M
internal
(U
ISO
)
120 VAC
Insulation tested with 1500 VAC
Current consumption
• From the backplane bus Max. 650 mA
Power dissipation of the
module
Typ. 3.3 W
Analog Value Generation
Measuring principle Integrative
Integration/conversion time/
resolution (per channel)
• Parameterizable
(Does not go into the
response time)
Yes
• Basic conversion time in
ms
22/25
• Additional conversion time
for measuring resistance,
in ms
Max. 200
• Resolution including sign 16/16 bit
• Noise suppression
for interference frequency
f1 in Hz
60/50
Smoothing of the measured
values
Parameters can be
assigned in 4 stages
Basic response time of module
(all channels enabled)
22/25 ms
Suppression of interference, Limits of Error
Noise suppression for f = n (f1 "1%),
(f1 = interference frequency) n = 1, 2, etc.
• Common-mode
interference (U
CM
< 120V)
• Series-mode interference
(peak value of interference
< rated value of the input
range)
> 100 dB
> 50 dB
Crosstalk between the inputs
> 70 dB
Operational limit (over entire temperature range, referred
to 0 to 60 C input range)
• RTD input " 1.0 °C
Basic error (operational limit at 25 °C, referred to input
range)
• RTD input " 0.5 °C
Temperature error (with
reference to the input range)
" 0.007%/K
Linearity error (with reference
to the input range)
" 0.2 °C
Repeat accuracy (in the steady
state at 25
°C, referred to the
input range)
" 0.2 °C
Status, Interrupts, Diagnostics
Interrupts
• Hardware interrupt when
limit has been exceeded
Parameters can be
assigned
• Diagnostic Interrupt Parameters can be
assigned
Diagnostic functions Parameters can be
assigned
• Group error display
– For internal fault
– For external fault
Red LED (INTF)
Red LED (EXTF)
• Diagnostic information can
be displayed
Possible
Data for Selecting a Sensor
Input range (rated values) input
resistance
• Resistance thermometer Pt 100, Pt 200, Pt 500,
Pt 1000, Ni 100,
Ni 1000
• Maximum input voltage for
voltage input (destruction
limit)
35 V continuous;
75 V for max. 1 s
(duty factor 1:20)
Connection of the sensor
• For measuring resistance
With three-conductor
terminal
Possible
With four-conductor
terminal
Possible
Characteristic linearization
• For resistance
thermometer
Pt 100,0,00385 to DIN
IEC 751
Ni 100, 0,00618 to DIN
43760
Unit for temperature
measurement
Degrees Celsius;
degrees Fahrenheit