Siemens Simatic M7-400 Manual do Utilizador Página 141

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 638
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 140
Digital Modules
4-19
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Technical Specifications of the SM 421; DI 32 x 24 VDC
Programming package
Associated programming
package
As of STEP 7 V 2.0
Dimensions and Weight
Dimensions W H D
(in millimeters)
25 290 210
Weight Approx. 600 g
Data for Specific Module
Number of inputs 32
Length of cable
Unshielded
Shielded
Max. 600 m
Max. 1000 m
Voltages, Currents, Potentials
Power rated voltage of the
electronics L+
24 VDC
Reverse polarity protection Yes
Power failure buffering None
Number of inputs that can be
triggered simultaneously
32
Isolation
Between channels and
backplane bus
Yes
Between channels and
power supply of the
electronics
No
Between the channels No
Permitted potential difference
Between the different
circuits
75 VDC / 60 VAC
Insulation tested with
Channels against
backplane bus and load
voltage L+
500 VDC
Current consumption
From the backplane bus Max. 30 mA
From supply voltage L+ Max. 30 mA
Power dissipation of the
module
Typ. 6 W
Status, Interrupts, Diagnostics
Status display Green LED per
channel
Interrupts None
Diagnostic functions None
Substitute value can be applied No
Sensor Selection Data
Input voltage
Rated value
For signal “1”
For signal “0”
24 VDC
11 V to 30 V
–3 V to 5 V
–30 V to 5 V as of
version 03
Input current
At signal “1” 6 mA to 8 mA
Input delay
At “0” to “1”
At “1” to “0”
1.2 ms to 4.8 ms
1.2 ms to 4.8 ms
Input characteristic curve To IEC 61131; type 2
Connection of two-wire BEROs Possible
Permitted bias current Max. 2.5 mA