Siemens Simatic M7-400 Manual do Utilizador Página 181

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 638
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 180
Digital Modules
4-59
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
4.16 Digital Output Module SM 422;
DO 16 24 VDC/2 A;
(6ES7422-1BH10-0AA0)
Characteristics
The digital output module SM 422; DO 16 24 VDC/2 A has the following
features.
16 outputs, isolated in two groups of 8
2 A output current
24 VDC rated load voltage
The status LEDs also indicate the system status even when the front connector is
not inserted.
!
Caution
To commission the module, the rated load voltage must be applied at least once to
each group of 8 outputs (e.g. connection of 1L and 3L). If voltage is not applied to
a group due, for example, to 1L and 2L failing, all the outputs switch off, even
those in the second group. The status LED continues to function in the same way.
Vista de página 180
1 2 ... 176 177 178 179 180 181 182 183 184 185 186 ... 637 638

Comentários a estes Manuais

Sem comentários