Digital Modules
4-52
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Technical Specifications of the SM 421; DI 16 120/230 VUC
Programming package
Associated programming
package
As of STEP 7 V 2.0
Dimensions and Weight
Dimensions W H D
(in millimeters)
25 290 210
Weight Approx. 650 g
Data for Specific Module
Number of inputs 16
Length of cable
Unshielded
Shielded
600 m
1000 m
Voltages, Currents, Potentials
Number of inputs that can be
triggered simultaneously
16 at 120 V
8 at 240 V
16 with fan
subassembly
Isolation
Between channels and
backplane bus
Yes
Between the channels Yes
In groups of 4
Permitted potential difference
Between M
internal
and the
inputs
230 VAC
Between the inputs of the
different groups
500 VAC
Insulation resistance 4000 VAC
Current consumption
From the backplane bus Max. 0.1 A
Power dissipation of the
module
Typ. 3.5 W
Status, Interrupts, Diagnostics
Status display Green LED per
channel
Interrupts None
Diagnostic functions None
Data for Selecting a Sensor
Input voltage
Rated value
For signal “1”
For signal “0”
120/230 VUC
79 to 264 VAC
80 to 264 VDC
0 VUC to 40 VUC
Frequency range 47 to 63 Hz
Input current
At signal “1”
At signal “0”
2 mA to 5 mA
0 to 1 mA
Input delay
At “0” to “1”
At “1” to “0”
5 to 25 ms
5 to 25 ms
Input characteristic curve To IEC 61131; type 1
Connection of two-wire BEROs
Permitted bias current
Possible
Max. 1 mA