Digital Modules
4-89
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Technical Specifications of the SM 422; DO 16 20-120 VAC/2 A
Dimensions and Weight
Dimensions W H D
(in millimeters)
25 290 210
Weight Approx. 800 g
Data for Specific Module
Number of outputs 16
Length of cable
Unshielded
Shielded
Max. 600 m
Max. 1000 m
Voltages, Currents, Potentials
Rated load voltage L+ 20 to 132 VAC
Permitted frequency range 47 Hz to 63 Hz
Total current of the outputs
Up to 40 C
Up to 60 C
With fan subassembly
Max. 16 A 24 A
Max. 7 A 16 A
Isolation
Between channels and
backplane bus
Yes
Between the channels
In groups of
Yes
1
Permitted potential difference
Between M
internal
and the
outputs
120 VAC
Between the outputs of the
different groups
250 VAC
Insulation tested with 1500 VDC
Current consumption
From the backplane bus
From load voltage L +
(without load)
Max. 600 mA
Max. 0 mA
Power dissipation of the
module
Typ. 20 W
Status, Interrupts, Diagnostics
Status display Green LED per
channel
Interrupts
Diagnostic Interrupt Parameters can be
assigned
Diagnostic functions Parameters can be
assigned
Group error display
For internal fault Red LED (INTF)
For external fault Red LED (EXTF)
Diagnostic
information readable
Possible
Substitute value can be applied Yes, programmable
Data for Selecting an Actuator
Output voltage
At signal “1” L1 (–1.5 Vrms)
Output current
At signal “1”
Rated value
Permitted range
2 A
100 mA to 2 A
Permitted surge current
(per group)
Max. 20 A/2 cycles
At signal “0” (leakage
current)
Max. 2.5 mA at 30 V
Max. 4.5 mA at 132 V
Output delay (for resistive load)
From “ 0” to “1” 1 ms
At “1” to “0” 1 AC cycle
Zero cross inhibit voltage Non-zero cross outputs
Size of the motor starter Max. size 5 to NEMA
Lamp load Max. 50 W
Parallel connection of 2
outputs
For redundant triggering of
a load
Possible (only outputs
of the same group)
To increase performance Not possible
Triggering a digital input Possible
Switch rate
For resistive load Max. 10 Hz
For inductive load
to IEC 947-5-1, DC 13
Max. 0.5 Hz
For lamp load 1 Hz
Short-circuit protection of the
output
Min. current required for
fuse to blow
Fuse 8A/125 V 2AG
(per output)
Min. 40 A
Max. response time Typ. 33 ms
Replacement fuses
Littelfuse
Fuse, 8 A, quick-acting
225.008