ENGINEERING INFORMATION AND INSTRUCTIONS
MICROMASTER
MICROMASTER Vector
MIDIMASTER Vector
SIEMENS DA 64 – 2002/2003
Version D 3/50
Time (s)
5
10
15
Permissible load
for
intermittent
duty
Permissible
load for
continuous duty
20
25
30
35
40
45
10%
50%
100%
Resistor type A B D E
Dimensions L x W x D (mm) 560 x 185 x 150 560 x 365 x 150 560 x 365 x 150 495 x 425 x 300
MIDIMASTER Vector
line supply voltage (V)
208 - 240 208 - 240 380 - 500 380 - 500
Resistance (W)
20 10 40 20
Surge power (kW) 7.5 15 15 30
Average power (kW) 1.25 2.5 2.5 5
Order No.
6SE3213-6SP87-0RA0 6SE3221-4SP87-0RA0 6SE3214-0TP87-0RA0 6SE3222-4TP87-0RA0
While braking, the electronic braking module discharges the energy of the motor and load into the external power resistors. The
lower the value of the external resistor, than the higher the braking power. The resistors can discharge a significant amount of
energy for a short period of time. However, if they are continually used, then the amount of energy which can be discharged is
significantly lower. In order to protect the resistors against overload, the EBU limits its own operating cycle (the ratio between the
ON time and the OFF time) to 10 %. This means that the maximum discharge power is reduced to the value shown in Fig. 3.
Drive inverter
EBU Associated resistances
Type Order No.
Minimum total
resistance for
each EBU
W
Order No.
Resist-
ance
W
Brief peak rated
value (5 s)
kW
Power for
a switch-
on
duration
=20 %
kW
Contin-
uous
rated
power
kW
Peak voltage
DC
V
MD(V)550/2 to 6SE3190-0CX87-2DA0 10 6SE3213-6SP87-0RA0 20 7.5 5 1.25 380
MDV4500/2 6SE3221-4SP87-0RA0 10 15 10 2.5 380
MD(V)750/3 to 6SE3190-0DX87-2DA0 20 6SE3214-0TP87-0RA0 40 15 10 2.5 950
MDV7500/3 6SE3222-4TP87-0RA0 20 30 20 5 950
MDV220/4 to
MD(V)3700/4
Your local Siemens sales office can provide you with information
about the range of electronic braking modules which are available for this drive inverter.
Braking resistors
Resistor type Order No. Cont. rated power
kW
Brief rated
peak power
kW
Resistance
W
Notes
A 6SE3213-6SP87-0RA0 1.25 7.5 20 Only for line supply voltages
B 6SE3221-4SP87-0RA0 2.5 15 10 208 V - 240 V
D 6SE3214-0TP87-0RA0 2.5 15 40 Only for line supply voltages
E 6SE3222-4TP87-0RA0 5 30 20 380 V - 500 V
If the electronic braking modules are used for high load moments of inertia (or extremely short ramp-down times), then it may be
necessary to connect additional resistors in parallel or to connect several electronic braking modules in parallel.
Fig. 4 - Cycle diagram for the electronic
braking module