ENGINEERING INFORMATION AND INSTRUCTIONS
MICROMASTER
MICROMASTER Vector
MIDIMASTER Vector
SIEMENS DA 64 – 2002/2003
Version D 3/36
Calculating a line reactor using an example.
u
K
= short-circuit rating of the transformer as a %
S
n
= rated apparent transformer rating
S
K
= system fault level
u
i
= ratio between the drive inverter rated power / system fault level (impedance)
P
U
= drive inverter power
[The apparent power of the drive inverter (S
drive inverter
= Ö3 * V * I
drive inverter
) can be neglected for this calculation, refer to the
values in brackets]
Calculation example: S
K
= (100 / u
K
) * P
n
u
i
= (100% / S
K
) * P
U
Transformer 1 V = 400V; S
n
= 100KVA; u
K
= 4%; drive inverter MDV 45000/3 =45KW (~ 58KVA)
S
K
= (100% / u
K
) * P
n
= (100% / 4%) * 100KVA = 2500KVA
u
i
= (100% / S
K
) * P
U
= (100% / 2500) * 45 = 1.8% (~ 2.3%) In this case, a line reactor is not required
Transformer 2 V = 400V; S
n
= 500KVA; u
K
= 4%; drive inverter MDV 45000/3 =45KW (~ 58KVA)
S
K
= (100% / u
K
) * S
n
= (100% / 4%) * 500KVA = 12500KVA
u
i
= (100% / S
K
) * P
U
= (100% / 12500) * 45 = 0.36% (~ 0.4%) In this case, a line reactor is required