Siemens Simatic M7-400 Manual do Utilizador Página 55

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 158
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 54
SIMATIC S7-400
Central processing units
SIPLUS PROFIBUS IF-964 DP module
6/55
Siemens ST 70 · 2013
6
Overview
To connect distributed I/O via PROFIBUS DP
Max. transmission rate 12 Mbit/s
Electrically isolated RS-485 interface
Connection via 9-pin Sub-D socket
Depending on the S7-400 CPU, one or two pluggable
PROFIBUS modules:
- CPU 414-3/416-3: 1 module
- CPU 417-4: 2 modules
Notes:
Can only be used with the CPUs 6AG1 416-3XR05-4AB0,
6AG1 416-3ER05-4AB0 and 6AG1 417-4XT05-4AB0.
SIPLUS extreme products are based on Siemens Industry
standard products. The contents listed here were taken from the
respective standard products. SIPLUS extreme-specific infor-
mation was added.
For further technical documentation on SIPLUS, see:
www.siemens.com/siplus-extreme
Ordering data
Order No.
SIPLUS PROFIBUS IF-964 DP
module
Order No. 6AG1 964-2AA04-7AB0
Order No. based on 6ES7 964-2AA04-0AB0
Ambient temperature range -25 ... +70 °C
Conformal coating
Coating of the printed circuit boards
and the electronic components
Technical data
The technical data of the standard
product applies except for the
ambient conditions.
Ambient conditions
Relative humidity
100%, condensation/frost permissi-
ble. No commissioning if condensa-
tion present.
Biologically active substances,
compliance with EN 60721-3-3
Class 3B2 mold and fungal spores
(excluding fauna). The supplied
plug covers must remain in place
over the unused interfaces during
operation!
Chemically active substances,
compliance with EN 60721-3-3
Class 3C4 incl. salt spray in accor-
dance with EN60068-2-52 (degree
of severity 3). The supplied plug
covers must remain in place over
the unused interfaces during opera-
tion!
Mechanically active substances,
compliance with EN 60721-3-3
Class 3S4 incl. sand, dust. The sup-
plied plug covers must remain in
place over the unused interfaces
during operation!
Air pressure (depending on the
highest positive temperature range
specified)
1080 ... 795 hPa (-1000 ... +2000 m)
see ambient temperature range
795 ... 658 hPa (+2000 ... +3500 m)
derating 10 K
658 ... 540 hPa (+3500 ... +5000 m)
derating 20 K
SIPLUS IF-964 DP
interface module
6AG1 964-2AA04-7AB0
(extended temperature range and
medial exposure)
Interface module with integrated
PROFIBUS DP master interface
Kap_06_eng.book Seite 55 Donnerstag, 2. Mai 2013 4:16 16
© Siemens AG 2013
Vista de página 54