SIMATIC S7-400
Modules for SIMATIC S7-400F/FH
SIPLUS IM 153-1/153-2
6/155
Siemens ST 70 · 2013
Overview (continued)
6
For technical documentation on SIPLUS, see:
www.siemens.com/siplus-extreme
Ambient conditions
Relative humidity 100%, condensation/frost permissi-
ble. No commissioning if condensa-
tion present.
Biologically active substances,
compliance with EN 60721-3-3
Class 3B2 mold and fungal spores
(excluding fauna). The supplied
plug covers must remain in place
over the unused interfaces during
operation!
Chemically active substances,
compliance with EN 60721-3-3
Class 3C4 incl. salt spray in accor-
dance with EN60068-2-52 (degree
of severity 3). The supplied plug
covers must remain in place over
the unused interfaces during opera-
tion!
Mechanically active substances,
compliance with EN 60721-3-3
Class 3S4 incl. sand, dust. The sup-
plied plug covers must remain in
place over the unused interfaces
during operation!
Air pressure (depending on the
highest positive temperature range
specified)
1 080 ... 795 hPa
(-1 000 ... +2 000 m)
see ambient temperature range
795 ... 658 hPa
(+2 000 ... +3 500 m)
derating 10 K
658 ... 540 hPa
(+3 500 ... +5 000 m)
derating 20 K
Ordering data
Order No.
IM 153-1 interface module
(extended temperature range and
medial exposure)
Slave interface for connecting an
ET 200M to PROFIBUS DP
• Standard temperature range 6AG1 153-1AA03-2XB0
IM 153-2 interface module
(extended temperature range and
medial exposure)
Slave interface for connecting an
ET 200M to PROFIBUS DP; also for
use in redundant systems
• High Feature, -25 ... +60 °C 6AG1 153-2BA02-2XY0
• High Feature, -40 ... +70 °C
6AG1 153-2BA02-7XB0
Active IM 153/IM 153 bus module
6AG1 195-7HD10-2XA0
(extended temperature range and
medial exposure)
For two IM 153-2 High Feature
modules for designing redundant
systems
Bus module for ET 200M
(extended temperature range and
medial exposure)
• To accommodate a power supply
and an IM 153 for the hot-swap-
ping function during RUN, incl. bus
module cover
6AG1 195-7HA00-2XA0
To accommodate two 40 mm wide
I/O modules for the hot-swapping
function
6AG1 195-7HB00-7XA0
To accommodate one 80 mm wide
I/O module for the hot swapping
function
6AG1 195-7HC00-2XA0
Accessories
See SIMATIC ET 200M
IM 153-1/153-2, page 6/153