SIMATIC S7-400
Central processing units
Fail-safe CPUs
CPU 416F
6/30
Siemens ST 70 · 2013
■
Overview
• For constructing a fail-safe automation system for plants with
increased safety requirements
• High-performance CPU in the top-end performance range
• Satisfies safety requirements up to SIL 3 acc. to IEC 61508
and Cat. 4 acc. to EN 954-1
• Standard and safety-related tasks can be performed with a
single CPU
• Multi-processor mode is possible
• Safety-related communication with distributed I/O devices
over PROFIBUS DP with the PROFIsafe profile
• Fail-safe I/O modules can be connected decentralized over
the integrated interfaces (DP and PN with CPU416F-3 PN/DP)
and/or through communication modules (CP443-5 Ext. and
CP443-1 Adv.)
• Standard modules for non-safety-related applications can be
operated centrally and decentralized
■
Technical specifications
6ES7 416-2FN05-0AB0 6ES7 416-3FS06-0AB0
CPU 416F-2 CPU416F-3 PN/DP
General information
Engineering with
• Programming package STEP 7 V5.3 SP2 or higher with hardware update,
Distributed Safety V5.2 SP2 or higher
STEP7 V5.5 or higher/iMap V3.0 + iMap STEP7 Add-on
V3.0 SP5 or higher
Supply voltage
24 V DC No; Power supply via system power supply No; Power supply via system power supply
Power losses
Power loss, typ. 4.5 W 6.5 W
Memory
Work memory
• integrated 5.6 Mbyte 16 Mbyte
• integrated (for program)
2.8 Mbyte 8Mbyte
• integrated (for data)
2.8 Mbyte 8Mbyte
Load memory
• expandable FEPROM, max. 64 Mbyte 64 Mbyte
• integrated RAM, max.
1Mbyte 1Mbyte
• expandable RAM, max.
64 Mbyte 64 Mbyte
CPU processing times
for bit operations, typ. 30 ns 30 ns
for word operations, typ. 30 ns 30 ns
for fixed point arithmetic, typ.
30 ns 30 ns
for floating point arithmetic, typ. 90 ns 90 ns
Counters, timers and
their retentivity
S7 counter
•Number 2 048 2 048
IEC counter
•present Yes Yes
S7 times
•Number 2 048 2 048
IEC timer
•present Yes Yes
Kap_06_eng.book Seite 30 Donnerstag, 2. Mai 2013 4:16 16
© Siemens AG 2013
Comentários a estes Manuais