Siemens Simatic M7-400 Manual do Utilizador Página 142

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 158
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 141
SIMATIC S7-400
SIPLUS interface modules
SIPLUS IM 460-0
6/142
Siemens ST 70 · 2013
6
Overview
Send interface module for centralized expansion up to 5 m
Transfer from P and K Bus
Plug into central controller
You may connect up to 8 expansion units (max. 4 per port)
Usable exclusively with IM 461-0
Note:
SIPLUS extreme products are based on Siemens Industry
standard products. The contents listed here were taken from the
respective standard products. SIPLUS extreme specific infor-
mation was added.
For technical documentation on SIPLUS, see:
www.siemens.com/siplus-extreme
Ordering data
Order No.
SIPLUS IM 460-0
Order number 6AG1 460-0AA01-2AB0
Order No. based on 6ES7 460-0AA01-0AB0
Ambient temperature range -25 ... +60 °C
Conformal coating
Coating of the printed circuit boards
and the electronic components
Technical data
The technical data of the standard
product applies except for the ambi-
ent conditions.
Ambient conditions
Relative humidity 100%, condensation/frost permissi-
ble. No commissioning if condensa-
tion present.
Biologically active substances,
compliance with EN 60721-3-3
Class 3B2 mold and fungal spores
(excluding fauna). The supplied
plug covers must remain in place
over the unused interfaces during
operation!
Chemically active substances,
compliance with EN 60721-3-3
Class 3C4 incl. salt spray in accor-
dance with EN60068-2-52 (degree
of severity 3). The supplied plug
covers must remain in place over
the unused interfaces during opera-
tion!
Mechanically active substances,
compliance with EN 60721-3-3
Class 3S4 incl. sand, dust. The sup-
plied plug covers must remain in
place over the unused interfaces
during operation!
Air pressure (depending on the
highest positive temperature range
specified)
1080 ... 795 hPa
(-1000 ... +2000 m)
see ambient temperature range
795 ... 658 hPa
(+2000 ... +3500 m)
derating 10 K
658 ... 540 hPa
(+3500 ... +5000 m)
derating 20 K
SIPLUS IM 460-0 interface module
6AG1 460-0AA01-2AB0
(extended temperature range and
medial exposure)
Send IM for central coupling up to
5 m; with C bus transfer
Accessories See SIMATIC IM 460-0,
page 6/135
Kap_06_eng.book Seite 142 Donnerstag, 2. Mai 2013 4:16 16
© Siemens AG 2013
Vista de página 141