Diagnostic data of signal modules
B.5 Diagnostic data of the analog input modules as of byte 2
S7-400 Automation System Module Data
Reference Manual, Edition 09/2009, A5E00850736-06
437
Bytes 9 to 24 of the SM 431; AI 16 x 16 bit
Data record 1 contains the channel-specific diagnostic data, starting at bytes 9 to 24. The
figure below shows the assignment of the diagnostic byte for a channel of the module.
Table B- 20 Diagnostic byte for a channel of the SM 431; AI 16 x 16 bit
Byte Bit Meaning
7 Overflow
6 Underflow
5 Reference channel error
4 Wire break
3 Short-circuit to M
2 0
1 0
Byte 9-24
0 Configuring/parameter assignment error
Bytes 2 and 3 of the SM 431; AI 8 x RTD x 16 bit
Table B- 21 Bytes 2 and 3 of the diagnostic data of the SM 431; AI 8 x RTD x 16 bit
Byte Bit Meaning
7 0
6 0
5 0
4 0
3 0
2 Operating mode 0: RUN; 1: STOP
1 0
Byte 2
0 0
7 0
6 Hardware interrupt lost
5 0
4 ADC/DAC error
3 0
2 EPROM error
1 0
Byte 3
0 0