Analog modules
5.26 Analog output module SM 432; AO 8 x 13 Bit (6ES7432-1HF00-0AB0)
S7-400 Automation System Module Data
340 Reference Manual, Edition 09/2009, A5E00850736-06
5.26.2 Commissioning the SM 432; AO 8 x 13 Bit
Parameters
You will find a description of the general procedure for assigning parameters to analog
modules in the respective sections.
For an overview of configurable parameters and defaults, refer to the "Parameters of analog
output modules" table.
Assigning parameters to channels
The parameters can be set separately at each output channel of SM 432; AO 8 x 13 Bit. You
can thus assign individual parameters to each output channel.
See also
General information about parameter assignment (Page 216)
5.26.3 Output ranges of the SM 432; AO 8 x 13 Bit
Configuration of analog output circuits
You can configure the outputs for operation as voltage or current outputs, or disable these.
You configure the output circuits at the "output type" parameter in
STEP 7
.
Unused channels
To make sure that unused output channels of SM 432; AO 8 x 13 Bit are de-energized, set
the "Output type" parameter to "deactivated" and leave the terminal open.
Output ranges
You program the output ranges for voltage and current outputs in
STEP 7
.
Table 5- 75 Output ranges of the SM 432; AO 8 x 13 Bit
Selected type of output Output range Description
Voltage 1 V to 5 V
0 V to 10 V
± 10 V
Current 0 to 20 mA
4 to 20 mA
± 20 mA
The digitized analog values are listed in
the section "Representation of analog
values for analog output channels" in
the voltage or current output range.