Digital modules
4.4 Diagnostics for digital modules
S7-400 Automation System Module Data
100 Reference Manual, Edition 09/2009, A5E00850736-06
4.4.2 Diagnostic messages of the digital modules
Overview
The table below gives an overview of the diagnostic messages for the digital modules with
diagnostics capability.
You can find out which diagnostic message each module is capable of in the Appendix
entitled "Diagnostic data of the signal modules".
Table 4- 6 Diagnostic messages of the digital modules
Diagnostic message LED Scope of diagnostics Programmable
Module error INTF/EXTF Module No
Internal error INTF Module No
External error EXTF Module No
Channel error INTF/EXTF Module No
External auxiliary voltage missing EXTF Module No
Front connector missing EXTF Module No
No module parameters INTF Module No
Incorrect parameters INTF Module No
Channel information available INTF/EXTF Module No
STOP mode - Module No
Internal voltage failure INTF Module No
EPROM error INTF Module No
Hardware interrupt lost INTF Module No
Parameter assignment error INTF Channel No
Short-circuit to M EXTF Channel Yes
Short-circuit to L+ EXTF Channel Yes
Wire break EXTF Channel Yes
Fuse blown INTF Channel Yes
Sensor supply missing EXTF Channel/channel
group
Yes
Load voltage L+ missing EXTF Channel/channel
group
Yes
Note
Prerequisite for detecting errors indicated by programmable diagnostic messages is an
appropriate configuration of the digital module in STEP 7.