Siemens S7-400PLC Especificações Página 238

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 486
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 237
Analog modules
5.15 Connecting loads/actuators to voltage outputs
S7-400 Automation System Module Data
238 Reference Manual, Edition 09/2009, A5E00850736-06
5.15 Connecting loads/actuators to voltage outputs
Connecting loads to a voltage output
Connecting loads to a voltage output is possible both in a 4-conductor and a 2-conductor
connection.
Note
The cables required to connect the analog output module are not drawn in the figures shown
below.
In other words, you must continue to read and follow the instructions in the section
"Connecting loads/actuators to analog outputs", which contains general information on
connecting sensors.
4-conductor connection of loads to a voltage output
You can use the 4-wire technique to achieve a high accuracy at the load by wiring the S- and
S+ sensor lines directly to the load. This results in direct measurement and correction of the
voltage at the load.
Faults or a voltage drop can result in a potential difference between the sensor lead S- and
the reference circuit of the analog circuit M
ANA
. This potential difference (U
CM
) must not
exceed the permissible value. A negative influence on the accuracy of the analog signal is
otherwise inevitable.
Vista de página 237