61
Accessory Ratings
Motor Operator Current Draw
Electrical Data for Remote Close Solenoid
Switch Contact Ratings
Undervoltage Release Ratings
Shunt Trip Ratings
Supply Voltage Motor Rating (Amperes)
120VAC
24VDC
48VDC
125VDC
3
3
3
3
Coil Voltage
Inrush Current
(Amperes)
Catalog Number
120V AC (60 Hz) 9.4A
SB4RCS120
SBRCS120
24V DC
48V DC
125V DC
20.0A
10.3A
3.6A
SB4RCS24, SBRCS24
SB4RCS48, SBRCS48
SB4RCS125, SBRCS125
Supply Voltage Ampere Rating
120V AC
240V AC
480V AC
24V DC
125V DC
10.0A
10.0A
6.0A
3.0A
0.5A
Catalog Number
Hold-in
Current
(Amperes)
Coil Voltage
SBUV12
SBUV24
SBUV48
SBUV125
SB4UV12
SB4UV24
SB4UV48
SB4UV125
0.12A
0.06A
0.03A
0.02A
12V DC
24V DC
48V DC
125V DC
SBUV120
SBUV240
SBUV480
SBUV600
SB4UV120
SB4UV240
SB4UV480
SB4UV600
0.02A
0.02A
0.02A
0.02A
120AC
240AC
480AC
600AC
Catalog Number
Inrush
Current
(Amperes)
Operating
Voltage
SBST12
SBST24
SBST48
SBST125
SB4ST12
SB4ST24
SB4ST48
SB4ST125
3.20A
3.10A
1.60A
0.64A
12V DC
24V DC
48V DC
125V DC
SBST120
SBST240
SBST480
SB4ST120
SB4ST240
SB4ST480
5.50A
3.60A
0.35A
120AC
240AC
480AC
Vista de página 63
1 2 ... 59 60 61 62 63 64 65 66

Comentários a estes Manuais