8
Installation instructions for systems breakers, trip units, and
rating plugs are presented in this section. Installation instruc-
tions for accessories that may be installed in the field are
presented in the Accessories section.
Installing Drawout Constructed SB Breakers
Drawout constructed SB breakers are designed to be installed
from the front into a switchboard with a minimum width open-
ing: 19 in. (1200A and 2000A frames), 20.36 in. (3200A frame),
and 28.34 in. (5000A frame). The stationary drawout element
may be secured in the switchboard at the front and rear to ver-
tical supports or at the top and bottom to horizontal supports.
Installing the Stationary Drawout Element
Prepare the switchboard for installation of the stationary
drawout element in accordance with the outline drawings
located in the Outline Dimension Drawings section starting on
page 36. The locations of the mounting holes are depicted on
the drawings.
Carefully uncrate the stationary drawout element. Remove all
packing material with the exception of the tie wraps holding
the extension rails in place. Depending upon the installation
scheme, it may be necessary to remove the tie wraps on the
extension rails just prior to securing the stationary drawout
element in the switchboard. If the stationary drawout element
is secured to a pallet, remove the securing device.
The bottom of the stationary drawout must be secured to the
switchboard using four 3/8-inch bolts. Additional mounting
hardware may be used to attach the top and front of the
stationary drawout but is not required.
The stationary drawout element can be manually lifted and
held in position as it is being installed. However, if preferred,
the two holes identified as lifting points on the outline drawing
may be used to attach a lifting device.
Attach lifting device to identified lifting points only.
NOTE: The two rear holes are located so that the station-
ary drawout element can be easily balanced as it is being
lifted by a crane or hoist. Do not lift the stationary
drawout element using only the two top front holes. If
preferred, the device can be lifted using all four top holes.
Lifting devices should not be attached to any other points. The
stationary drawout element should not be lifted by the primary
stabs.
Lift the stationary drawout element into position and secure it
in place. Remove the lifting device.
Remove the tie wraps securing the extension rails. Check to
ensure that no packing or other foreign material impedes rail
movement.