22
Operating Instructions
Manipulating the Moveable Drawout Element
CAUTION
!
Unlocked Position to Test Position
Racking the moveable drawout element from the Unlocked
position to the Test position engages the moveable drawout
element with the stationary drawout element. The physical
position of the moveable drawout element will be unchanged.
Complete the steps that follow to rack the moveable drawout
element from the Unlocked position to the Test position.
NOTE: If extension rails are pulled out, push them in until
they hit a solid stop.
1. Push in the directional shift lever. This is the racking-in position.
2. Pull the release lever down to the release-disengaged position.
(Illustrated beneath padlock device.) If the breaker contacts are
closed, pulling the release lever down will trip the breaker.
3. Pump the racking pump handle until the moveable drawout element
has reached the Test position.
4. When the moveable drawout element reaches the Test position, the
release lever will automatically return to the release-engaged (up)
position, the racking pump cannot be pumped, and the position
indicator will display that the moveable drawout element is in the
Test position.
To avoid damaging the racking mecha-
nism, always pull the release lever
before racking the moveable drawout
element.