General Information
CAUTION
!
Universal Test Kit
Operating Instructions
NOTE: Detailed instructions are supplied with the TS-31
kit.
1. Remove electrical loads from circuit breaker.
2. Plug TS-31 test set into a grounded 120VAC receptacle and turn it on.
The identifying turn-on message appears
3. Select the appropriate ribbon cable assembly and connect it between
the TS-31 and the circuit breaker. Check alignment and polarity.
4. Comply with the prompting messages. If you require guidance, refer
to the instructions shipped with the TS-31 test set.
5. Enter the appropriate breaker settings when prompted. If the breaker
includes instantaneous pickup, short-time functions, or ground fault,
enter the appropriate breaker settings.
NOTE: Entering the wrong data will cause false tests and
results.
6. Enter the test and phase you want tested. The TS-31 reports the type
of test you selected and gives you a chance to abort the test. If you
press the letter A to abort, you are given new options.
7. Comply with the prompt to start the test. The test can require a few
seconds or several minutes, depending on which procedure is
running.
NOTE: If the breaker trips during a test, reset it before
continuing.
The last setting entered into the TS-31appears in brackets on
the second line of the display. If you do not want to change an
existing setting, press ENTER. If you want to change a setting,
type in the new setting and press ENTER.
Error Messages
An error message may appear if the test set senses that cur-
rent is not flowing correctly in the breaker. This can occur
when there is an open or short circuit between the TS-31 and
the breaker trip unit. Error messages also may appear:
• If you enter a type of test that is not available on the breaker
being tested.
• If you select a ground-fault test and the trip unit does have
ground fault.
• If you enter a setting value that does not exist.
Running successive high-current, long-time tests can overheat
the test set. The unit protects itself from damage by prevent-
ing further tests until it has cooled down. The display indicates
when testing can resume.
The TS-31 warns you of possible fault coverage conflicts. For
example, conflicts can occur if the short-time and instanta-
neous pickup settings overlap or interfere with one another.
NOTE: For trip unit values, refer to the information sheets
supplied with the TS-31 kit.
External Accessories
Universal Test Kit (TS-31)
Remove electrical loads from the circuit
breaker to be tested prior to performing
tests. Failure to do so can produce
erroneous results and possible electrical
malfunction.