62 Siemens Simatic S7 Driver Online Help
To send block writes through FIX/iFIX
[1] Enable block writes in the datablock you want to use.
[2] Create a Digital Output block with the following address:
!Send:DataBlockName
Note that only datablock names are valid with the !Send control address. You cannot
trigger block writes using either of the following items:
Channel and device names in place of a datablock name.
Analog Output blocks in place of a Digital Output block.
See Also
Sending Multiple Writes to a Datablock
Feature: Advanced Diagnostics
The SI7 I/O driver supports statistics, a datascope, and a data monitor to help you
troubleshoot any errors or problems you may encounter. The statistics provide the
number of timeouts, retries, and overruns for the driver and each defined channel,
device, and datablock. The datascope lets you see a portion of the characters being
transmitted and each message received. To display the datascope, select Datascope
from the Options menu.
You can enable the datascope for individual channels, devices, or datablocks.
To enable the datascope for a channel, device, or datablock
[1] Right-click the channel, device, or datablock you want to enable in the Tree
Browser.
[2] Select Datascope On from the pop-up menu that appears.
IMPORTANT: You can only access the datascope from the local server. Accessing
the datascope from a remote node is not supported.
The datascope is a troubleshooting utility. Do not leave it running during production.