Chapter 14. Troubleshooting 227
Power Tool
[1] Verify that each datablock address is valid and exists. The most common error
for datablocks is requesting memory locations that are not configured in the
hardware.
[2] Use the Last Error field in the datablock statistics to determine which
datablocks are experiencing an error. If you see text in the field, use the topic
Error Codes for a description of this error and how to resolve the problem.
[3] Use the Last Simatic Error field to determine if SIMATIC NET is reporting an
error. If it is, use the text underneath the field to correct the problem. If the
error text does not provide enough information to help you resolve the issue,
contact Siemens support at 1-800-964-4114 Monday through Friday during
regular business hours or 1-800-241-4453 for emergency after hours service.
If you are not receiving errors in the statistics section
Refer to Using Primary and Secondary Poll Rates with Access Time to ensure
the datablock’s access time is set correctly.
See Also
Checking Communication | The driver communicates to some but not all of my
devices
I cannot connect to a remote server
If you cannot connect to a remote server
Verify that you have entered the correct name or IP address for the remote
server.
Verify that you have an account on the remote computer.
If the server resides in a Windows domain, verify that the local computer is
logged into the same domain as the remote computer.
Confirm that the security for using the server remotely has been set up. Refer
to Setting up Security to use the I/O Server Remotely for more information.