Appendix
A.2 System alarms
TP 270, OP 270, MP 270B (WinCC flexible)
A-14 Operating Instructions, Edition 03/2004, 6AV6691-1DD01-0AB0
Number Effect/cause Remedy
160012 There is no connection to the server because the
server identification (CLS-ID) cannot be
established.
Values cannot be read or written.
For example, check if
The server name is correct
The computer name is correct
The server is registered
Note for experienced users:
Interpret the value from HRESULT.
160013 The specified server was started as InProc Server.
This has not been released and may possibly lead
to incorrect
!
e-establ because the server is
running in the same process area as the WinCC
flexible Runtime software.
Configure the server as OutProc Server or Local Server.
160014 Only one OPC server project can be started on a
PC/MP. An error message appears when an
attempt is made to start a second project.
The second project has no OPC server functionality
and cannot be located as an OPC server from
external sources.
Do not start a second project with OPC server
functionality on the computer.
170000 S7 diagnostic alarms are not displayed because it
is not possible to log on to the S7 diagnostics with
this unit. The service program is not supported.
-
170001 The S7 diagnostics buffer cannot be displayed
because communication with the PLC has been
switched off.
Switch the PLC online.
170002 The S7 diagnostics buffer cannot be displayed
because reading in the diagnostics buffer (SSL)
was aborted due to an error.
-
170003 The display of an S7 diagnostic alarm is not
possible. An internal error %2 has been reported.
-
170004 The display of an S7 diagnostic alarm is not
possible. An internal error with error class %2 and
error number %3 has been reported.
-
170007 It is not possible to read in the S7 diagnostics buffer
(SSL) because it was aborted with an internal error
class %2 and error code %3.
-
180000 A component/OCX receives configuration data with
a version identification which is not supported.
Install a newer component.
180001 The system is overloaded because too many
actions have been activated simultaneously. Not all
the actions can be executed; some are rejected.
Several remedies are available:
Increase the configured cycle times or basic clock.
Generate the alarms slower (polling).
Trigger the scripts and functions at greater intervals.
If the alarm appears more frequently:
Restart the HMI device.
180002 The screen keyboard could not be activated.
Possible cause:
The file TouchInputPC.exe" was not registered
due to an incorrectly executed Setup.
Reinstall WinCC flexible runtime.
190000 It is possible that the tag will not be updated. -
190001 The tag is updated following an error status after
the cause of the last error state has been
eliminated (return to normal operation).
-