Appendix
A.2 System alarms
TP 270, OP 270, MP 270B (WinCC flexible)
A-8 Operating Instructions, Edition 03/2004, 6AV6691-1DD01-0AB0
Number Effect/cause Remedy
70040 The syntax of the e-mail address is incorrect or
contains illegal characters.
-
80001 The specified log is filled to the maximum (in
percent) and must be stored elsewhere.
Store the file or table by executing a move or copy
function.
80002 A line is missing in the specified log. -
80003 The copying process for logging was not
successful.
In this case, it is also advisable to check any
subsequent system alarms.
-
80006 Logging is not possible, resulting in a permanent
loss of the functionality.
In the case of databases, check whether the
corresponding data source exists and restart the system.
80009 A copying action has been completed successfully. -
80010 The storage location was incorrectly entered in
WinCC flexible, resulting in a permanent loss of the
functionality.
Configure the storage location for the respective log
again and restart the system when full functionality is
required.
80012 Log entries are stored in a buffer. If the values are
read to the buffer faster than they can be physically
written (using a hard disk, for example),
overloading may occur and recording is then
stopped.
Archive fewer values.
or:
Increase the logging cycle.
80013 The overload status no longer applies. Archiving
resumes the recording of all values.
-
80014 The same action was triggered twice in quick
succession. Since the process is already in
operation, the action is only carried out once.
-
80015 This system alarm is used to report DOS or
database errors to the user.
-
80016 The logs are separated by the system function
"CloseAllLogs" and the incoming entries exceed the
defined buffer size.
All entries in the buffer will be deleted.
Reconnect the logs.
80017 The incoming entries exceed the defined buffer
size. This can be caused, for example, by several
copying actions being activated at the same time.
All copy jobs will be deleted.
Stop the copy action.
80018 After executing the system function "OpenAllLogs",
all connections between WinCC flexible and the
logs have been
!
e-established.
Entries will be rewritten into the logs.
-
80019 All connections between WinCC flexible and all
logs have been severed, for example, after
executing the system function "CloseAllLogs".
Entries will be written to the buffer and written into
the logs when a connection is re-established.
There is no connection to the storage location and
the data medium may be in the process of being
exchanged.
-
80020 The maximum number of simultaneously activated
copy actions has been exceeded. Copying is not
executed.
Wait until the current copying actions have been
completed and restart the last copy action.