Appendix
A.2 System alarms
TP 270, OP 270, MP 270B (WinCC flexible)
Operating Instructions, Edition 03/2004, 6AV6691-1DD01-0AB0
A-11
Number Effect/cause Remedy
130002 The action was not executed. Close the other programs.
Delete files no longer required from the hard disk.
130003 No data medium is inserted. The process is
stopped.
For example, check if
The correct data medium is being accessed
The data medium is inserted
130004 The data medium is write-protected. The process is
stopped.
Check whether access has been made to the correct
storage medium. Remove any write protection.
130005 The file is write-protected. The process is stopped. Check whether access has been made to the correct file.
Modify the file attributes, if necessary.
130006 No access to file is possible. The process is
stopped.
For example, check if
The correct file is being accessed
The file exists
Another action is preventing simultaneous access to
the file
130007 The network connection is interrupted.
Data records cannot be saved or read over the
network connection.
Check the network connection and correct the reason for
the disruption.
130008 The storage card is not available.
Data records cannot be saved or read to the
storage card.
Insert the storage card.
130009 The specified directory is not on the storage card.
The files that are saved in this directory are not
saved when the HMI device is switched off.
Insert the storage card.
130010 The maximum nesting depth can be exhausted, for
example, when a value change in a script results in
the initiation of another script. The second script in
turn has a value change resulting in the initiation of
another script and so on.
The configured functionality is not provided.
Check the configuration.
140000 Online connection to the PLC has been
successfully established.
-
140001 Online connection to the PLC has been
disconnected.
-
140003 No tag updating or writing is executed. Check the connection and whether the PLC is switched
on.
Check the parameter definitions in the Control Panel
using "Set PU/PC interface".
Restart the system.
140004 No tag updating or writing is executed because the
access point or the subrack configuration is
incorrect.
Verify the connection and check whether the PLC is
switched on.
Check the access point or the subrack configuration
(MPI, PPI, PROFIBUS) in the Control Panel with "Set
PU/PC interface".
Restart the system.
140005 No tag updating or writing is executed because the
address of the HMI device is incorrect (possibly too
high).
Use a different HMI device address.
Verify the connection and check whether the PLC is
switched on.
Check the parameter definitions in the Control Panel
using "Set PU/PC interface".
Restart the system.