N2 Bus
Standard NCU
UNT
RS-232
N1LAN
Metasys
Integrator Unit
i
n
RS-485
(two wire)
9300
Power
Meter
Isolated
Multidrop
Converter
9600
Power
Meter
9500
Power
Meter
Note: If you use a UPM enclosure, you must install the Metasys Integrator unit
300 Series in a two high enclosure (EN-EWC25-0) rather than a one high
enclosure (EN-EWC13-0) as shown in the figures in this application note.
Figure 4: Siemens and Metasys System Companion Integration
Using MODBUS Communication
To integrate Siemens SEAbus equipment, you need:
Component
Requirements
• Siemens RS-232 to RS-485 Isolated Multi-Drop converter
(18-658-582-537)
• proper Siemens devices and communication hardware
• RS-232 cable for connecting the converter to the Metasys Integrator
unit (cable comes with the Siemens converter 18-658-582-537)
• Belden® 8723 or equivalent RS-485 four-wire cable (for connecting
the adapter to Siemens devices)
• Metasys Integrator unit
• N2 Bus (for connecting the integrator unit to the Metasys or
Companion Network)
• portable Personal Computer (PC) for downloading vendor
communication tables (.VCT files) and network setup information into
the Metasys Integrator unit, and for running diagnostics
• cable for connecting portable PC to the Metasys Integrator unit
• the correct vendor communication table (.VCT file) to download into
the Metasys Integrator unit (supplied on Metasys Integrator unit
CD-ROM)
Metasys Integrator—Metasys Integrator Siemens Application 5