The following table shows the points available for mapping in the Siemens
Model 9500/9600 Power Meter:
9500/9600
Power Meter,
MODBUS
Network
Table 8: Siemens 9500/9600 Power Meter, MODBUS Network
NPT
1
NPA
2
Unit Description
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
Vrms
Vrms
kVa
%
%
Hz
kW
kVAR
kVA
%
kWh
Voltage LN Average
Voltage LL Average
Average Current
Voltage Unbalance
Current Unbalance
Frequency
Current 4 [14]
kW Total
kVAR Total
kVA Total
Power Factor Total
kWh Rec
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Volt
Volt
Volt
Volt
Volt
Volt
Amps
Amps
Amps
kW
kW
kW
kVAR
kVAR
kVAR
kVA
kVA
kVA
+/-%
+/-%
+/-%
Volts
Amps
kW
Voltage at Phase A
Voltage at Phase B
Voltage at Phase C
Voltage at Phase AB
Voltage at Phase BC
Voltage at Phase CA
Current at Phase A
Current at Phase B
Current at Phase C
kW at Phase A
kW at Phase B
kW at Phase C
kVAR at Phase A
kVAR at Phase B
kVAR at Phase C
kVA at Phase A
kVA at Phase B
kVA at Phase C
Power Factor A
Power Factor B
Power Factor C
Voltage LN Average Maximum
Current Average Maximum
kW Total Maximum
1 Network Point Type
2 Network Point Address
Continued on next page . . .
To get the hardware
reference for
mapping points to
CS object attributes
(via the software
model), combine
the NPT (Network
Point Type) and
NPA (Network Point
Address). For
example, the
hardware reference
for the Average
Cuurent is AI3.
Metasys Integrator—Metasys Integrator Siemens Application 19