7ML19985BE02 SITRANS LU01 – INSTRUCTION MANUAL Page 59
mmmmm
Parameters
P702 Filling Indicator
The fill rate required to activate the LCD Filling indicator ( ).
This value (in Units (P005) or % of Span (P007) per minute) is automatically set to 1/10 of
the Max Fill Rate (P700).
P703 Emptying Indicator
The empty rate required to activate the LCD Emptying indicator ( ).
This value (in Units (P005) or % of Span (P007) per minute) is automatically set to 1/10 of
the Max Empty Rate (P701).
P704 Rate Filter
Damps Rate Value (P707) fluctuations.
Enter the time or distance interval over which the Rate Value is to be calculated before
the display updates.
This is automatically altered along with Maximum Process Speed (P003).
This value automatically alters the Rate Update Time (P705) and / or Rate Update
Distance (P706). Alternatively, these parameter values may be altered independently.
Values Range: -999 to 9999
Altered by P003 Maximum Process Speed
Related
P005 Units
P007 Span
P700 Max Fill Rate
Values Range: -999 to 9999
Altered by P003 Maximum Process Speed
Related
P005 Units
P007 Span
P701 Max Empty Rate
Values
0 Rate display not required
Filtered Output
1 Continuously filtered and updated
Interval Output
2 1 minute or 50 mm (2 in)
3 5 minutes or 100 mm (3.9 in)
4 10 minutes or 300 mm (11.8 in)
5 10 minutes or 1000 mm (39.4 in)
Alters P707 Rate Value
Altered by P003 Maximum Process Speed
Related P705 Rate Update Time/ P706 Rate Update Distance