Page 58 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02
Parameters
If Temp Source (P660) is set to any value other than Fixed Temp, the value displayed is the
temperature measured. If Temp Source is set to Fixed Temp, the P661 value is displayed.
Rate (P700 to P707)
These parameters determine how material level changes are reported.
P700 Max Fill Rate
Adjusts the SITRANS LU01 response to increases in the actual material level (or advance
to a higher Failsafe Material Level, P071).
Enter a value slightly greater than the maximum vessel filling rate. This value, in Units
(P005) or % of Span (P007) per minute, is automatically altered when Maximum Process
Speed (P003) is altered.
P701 Max Empty Rate
Adjusts the SITRANS LU01 response to decreases in the actual material level (or advance
to a lower Failsafe Material Level, P071).
Enter a value slightly greater than the maximum vessel emptying rate. This value, in Units
(P005) or % of Span (P007) per minute, is automatically altered when Maximum Process
Speed (P003) is altered.
Values Range: 0.000 to 9999
Altered by • P003 Maximum Process Speed
Related
•P005 Units
•P007 Span
• P071 Failsafe Material Level
P003 Value Meters/Minute
10.1
2 1
310
Values Range: 0.000 to 9999
Altered by • P003 Maximum Process Speed
Related
• P005 Units
• P007 Span
• P071 Failsafe Material Level
P003 Value Meters / Minute
10.1
2 1
310