Page 32 SITRANS LU01 – INSTRUCTION MANUAL 7ML19985BE02
Parameters
Application Parameters
Volume (P050 to P055)
Use these parameters to enable the SITRANS LU01 to show readings based on vessel
volume (rather than level).
P050 Tank Shape
Enter the Tank Shape value matching the monitored vessel or wet well.
When Operation is level (P001 = 1), liquid (material) volume is calculated. Alternatively,
when Operation is space (P001 = 2), remaining vessel capacity is calculated. In RUN
mode, readings are displayed in percent of maximum volume. To convert readings to
volumetric units, see
Maximum Volume (P051)
.
Values
# Shape Description
0*
volume calculation not required
(preset)
1 Flat Level Bottom
2 Cone/Pyramid Bottom
3 Parabola Bottom
4 Half Sphere Bottom
5 Flat Sloped Bottom
6Flat Ends