Display, Operation
Multifunction Pushbuttons
Pushbuttons with room temperature controllers
1/13
Siemens ET G1 · 10/2008
1
Technical specifications
Type Description
UP 231/3 UP 231/3 pushbuttons
• Vertical operation
Two wide inner rocker buttons
• Function can be user-assigned: switching OVER, switching
ON/OFF, switching ON/OFF and dimming, shutter/blind, value
transmission, store and call up scenes of up to four 1-bit scenes
in conjunction with scene module
Short and long button press for ON/OFF/OVER, BRIGHTER/
DARKER for dimming, and UP/DOWN and adjustment of slats
for shutter/blind control
• Operation/status indication over one LED per rocker button
• Integrated room temperature sensors and controllers for
heating only, cooling only or combined heating/cooling
Control over an algorithm for adaptive control and/or a two-point
algorithm
• With monitoring of room temperature over a room temperature
sensor integrated in the controller and an external room temper-
ature sensor connected to the KNX, and with adjustable weighting
between the measured indoor and outdoor temperature
Two narrow outer rocker buttons for setpoint offsetting in comfort
mode and one for switching between comfort and standby
mode
Operating modes that can be switched over KNX: comfort
mode, standby mode, night mode, frost or heat protection
mode, with adjustable offset of the room temperature setpoint
for comfort mode
Adjustable dead zone, selectable either symmetric to the
setpoint for comfort mode or between the heating and cooling
setpoint for comfort mode
Selectable sequence control for heating and cooling mode
(required e.g. for the combination of floor and radiator heating)
Output of the control variable(s) either as ON/OFF switch command
or as positioning command in the range 0 % ... 100 %, with
LEDs for the indication of the current operating mode and
setpoint offsetting
• For plugging onto a UP 114 bus coupling unit
• Dimensions (H x W x D): 65 x 65 x 15 mm
UP 252H UP 252H multifunction controllers
For direct control of the valves and the fan of the fan coil or a
split unit
Preselection of the required control function of directly connected
heaters/refrigerators using the ETS
• Integrated room temperature sensors
• P or PI control of the room temperature for heating, cooling or
heating and cooling mode
• For adjustment of comfort, pre-comfort, night and protection
modes over the bus
• Adjustment of temperature setpoint for comfort mode
• Adjustment of temperature setpoints over the ETS for all other
operating modes
• Fixed dead zone (1K) between heating and cooling in comfort
mode
• Presence pushbutton to locally switch over between comfort
and pre-comfort and for extending comfort mode through
activation of the night mode
• Pulse-width modulated control signal output
Eight operator buttons for the manual adjustment of the comfort
temperature setpoint, for the selection of the operating mode
and ventilator speed step and the ON/OFF switching of a load
(e.g. room lighting)
A red status LED per operator button
An LCD with three digits for the representation of the current
setpoint or room temperature
• A binary input for the direct connection of a floating window
contact
A binary input for 12 V DC for the direct connection of a presence
detector
An analog input for the optional connection of a temperature
sensor mounted in the intake air flow of a ventilator convector
(NTC sensor, 10 kOhm at 25 °C),
Five binary outputs 24 V AC (relay contacts for 2 A, p.f. = 1) for
the control of electrothermal valve actuators, for the switching
of ventilator speed steps, etc. depending on the configured
application.
Integrated bus coupling units
• Bus connection via bus terminal
• Integrated power supply for 24 V AC
Double hanging bracket for mounting on two combined hollow-
wall or flush-mounting boxes with at least
58 mm and at least
40 mm depth or an equivalent double flush mounting box
ET_G1_2009_en.book Seite 13 Freitag, 28. November 2008 9:50 09
© Siemens AG 2008