Application Examples
System overview
18/5
Siemens ET G1 · 10/2008
18
System data
Bus cable
Cable type mm
2
YCYM 2 x 2 x 0.8
One core pair (red, black) for signal transmission and power supply,
One core pair (yellow, white) for additional applications (SELV or voice)
Cable length
Cable lengths of one line in total (core diameter: 0.8 mm) m Max. 1000 (including all junctions)
Length between two bus devices m Max. 700
Length between bus device and
power supply unit (320 mA)/reactor
m Max. 350
Length between power supply unit (320 mA) and reactor Side-by-side mounting necessary
(on standard mounting rail with integrated data rail)
Bus devices
Number of areas Max. 15
Number of lines per area Max. 15
Number of bus devices per line Max. 64
Topology Line, star or tree structure
Power supply
Power supply V DC 24 (SELV safety extra-low voltage)
Power supply units per line One power supply unit (160, 320 or 640 mA)
Power supply units per line for high current demand Max. two power supply units at a distance of at least 200 m
Transmission
Transmission technology Distributed, event-controlled, serial, symmetric
•Baud rate bit/s 9600
Device features (unless otherwise specified)
Degree of protection according to EN 60529 IP 20
Protective measure Bus: safety extra-low voltage SELV 24 V DC
Overvoltage category III
Rated insulation voltage U
i
V 250
Degree of pollution 2
EMC requirements Complies with EN 50081-1 and prEN 50082-2 (severity 3),
prEN 50090-2-2, KNX/EIB manual
Resistance to climate prEN 50090-2-2, KNX/EIB manual
Operating conditions
Application For fixed installation indoors, for dry rooms and
installation in heavy-current distribution boards
Ambient operating temperature °C -5 to +45
Humidity in operation % Max. 93
Storage temperature °C -40 to +55
Humidity in storage % Max. 93
Certification KNX/EIB certified
CE marking Compliant with EMC Directive (residential and non-residential buildings),
Low Voltage Directive