3-27
SIMATIC 545/555/575 System Manual
Installing 505 System Hardware
Figure 3-14 shows the installation of a module in a Series 505 base.
Minimum torque: 2.6 inlb (0.3 Nm)
Maximum torque: 5.2 inlb (0.6 Nm)
Figure 3-14 Installing and Removing Modules in a Series 505 Base
Two types of terminal block connectors are available for SIMATIC 505 input
and output modules: the front-accessible 25877058011 terminal block and
the side-accessible 25877058010 terminal block, as shown in Figure 3-16.
Figure 3-15 shows the wire gauge and stud sizes you can use for the
terminal blocks. Note in particular the maximum torque specification for
the terminal block screws of 5.0 in-lb (0.56 N-m).
Stud Size: #4 (2.5mm)
Amp Part#: 321462
Use with connector 25877058010
1cm
(0.39 in.)
Wire Gauge: 1226 (both connectors)
Max. Width: 5.54 mm (.218 in.)
Max. Width: 4.62 mm (.182 in.)
Stud Size: #4 (2.5mm)
Amp Part#: 327891. (Specify 2pt. Connector)
Use with connector 25877058010
Maximum torque:
5.0 in-lb (0.56 N-m)
Note: When using small gauge or finely stranded wire, tin the wire ends or use an appropriately
sized pin contact (ferrule) for the best possible connection. Do not exceed the specified maximum
torque on the terminal block screws.
Figure 3-15 Wire Gauge and Stud Sizes for Input/Output Terminal Blocks