Installing Remote Base ControllersRBCs SIMATIC 545/555/575 System Manual
PPX:5056870 RBC (continued)
Switch 11 on the dipswitch controls the display mode of the RBC Status
Display to show either station address or module status.
When switch 11 is set to 1, the station address of the RBC is displayed
as a three-digit number, one digit at a time. The display goes blank for
a short period of time between each digit and for a long period after the
last digit. For example, if the RBC station address is 18, it will be
displayed according to this pattern:
0 (short pause) 1 (short pause) 8 (long pause)
0 (short pause) 1 (short pause) 8 (long pause) . . .
The three-digit pattern repeats until the mode is changed.
When switch 11 is set to 0, the status of the RBC is displayed,
according to the codes shown in Table 5-8.
NOTE: When switch 11 is set to display the RBC status, a decimal point on
the status display indicates that the 50X Ignore Mismatch Mode parameter
is enabled. The point appears before the status code, as shown below.
50X Ignore Mismatch
Mode: Enabled
50X Ignore Mismatch
Mode: Disabled
If the 50X Ignore Mismatch Mode is disabled (the default value that
conforms to the DP standard), the RBC status display does not show a
decimal point. For more information about this parameter, see page 5-24.
The Status Display mode switch is read periodically during operation. The
switch may be changed at any time.
Table 5-8 505 PROFIBUS-DP RBC Status Codes
Display Definition
Communications
to This RBC
Comment/Action
0 Module Ready OK
Fully operational. No errors detected.
Action: None.
1 Diagnostic Failure None
Serious malfunction.
Action: Place the system in a safe state and
consult Siemens Technical Support. (In the
U.S.A., call 4234612522.)
2 Module Mismatch OK
I/O modules installed in this base do not
match the expected configuration in the
PROFIBUS-DP master.
Action: Compare the actual configuration of
the base against the configuration expected
by the PROFIBUS-DP master.