5-13
Installing Remote Base ControllersRBCs
SIMATIC 545/555/575 System Manual
Table 5-4 RBC Status Codes (continued)
Display Definition
Communications
to this RBC
Comment/Action
4 RAM Parity Error None
The RBC has detected an internal RAM
parity error.
Action: Serious malfunction. Place the
system in a safe state and consult Siemens
Technical Support. (In the U.S.A., call
4234612522.)
5 Standby, No Configuration OK
Standby RBC in dual-media application has
no configuration.
Action: Configure the RBC.
6 Address Mismatch OK
Address switch setting is incorrect.
Dual-media RBCs need to have the same
address switch setting.
Action: In a dual-media application, set both
address switches to the same address. If
they are at the same address, consult
Siemens Technical Support. (In the U.S.A.,
call 4234612522.)
7
Communication Good, No
Configuration
OK
RBC has no configuration.
Action: Configure the RBC.
8 Watchdog Time Out None
Hardware watchdog timeout that
immediately resets the RBC.
Action: Serious malfunction. Place the
system in a safe state and consult Siemens
Technical Support. (In the U.S.A., call
4234612522.)
C Standby, Configuration OK
Standby RBC in dual-media application is
ready to take over. I/O configuration is OK.
Action: None.
blank Blank, No Code Displayed None
No power to base, or serious malfunction.
Action: Check power to base. If base power is
OK, place the system in a safe state and
consult Siemens Technical Support. (In the
U.S.A., call 4234612522.)