How to configure an Anybus PROFIBUS Slave module with a Siemens Step7 PLC
SCM-7032-026
Rev 2.1
Diagnostics in Step7
Step7 and the HW Config program provide diagnostic possibilities via the PROFIBUS master over the
network. Start with going online by clicking on the button n in Figure 33. Then right-click on o and chose
“Module Information” and the diagnostic function will be started. The window p will be displayed and
available diagnostics can be read out.
What diagnostics that is available depends on the application. In standard mode there are no application
specific diagnostics available. All the standard PROFIBUS diagnostics are supported and information
regarding this can be found in the online documentation of Step7. Application specific diagnostics, error
codes etc. can be found in the documentation of the application.
If the message shown in the window p appears the reason can be the following:
The Anybus module is not attached properly to the PROFIBUS network. Check cabling.
The node address of the Anybus module does not match the address set in the Simatic Config
program.
The Anybus module is faulty and does not start up properly. Check the LEDs on the Anybus module.
Figure 33 Step7 Hardware diagnostics.