How to configure an Anybus PROFIBUS Slave module with a Siemens Step7 PLC
SCM-7032-026
Rev 2.1
1.5. Communicator configuration
Start the Anybus Communicator Config Tool. The module is configured for PROFIBUS and generic data
mode as shown below. The I/O size is set to 2 bytes in this example.
Figure 19 Bus type setup.
Figure 20 Protocol mode configuration.
The sub network is configured as seen in the figure below. The values are left at the default except for the
update time for the produce transaction, in this case it is set to 500 ms. Also the bit rate is set to 19200 bits/s.