Ten valuable tips on assembly
The following 10 tips should be followed to make sure nothing goes wrong during as-
sembly:
Tip 3 – Slaves
Each slave address must only be used once. Only use addresses 1 to 31 or
1A to 31B in A/B technology (Specification 2.1). Please note: All modules
that contain the SAP 4.1 chip can be readdressed any number of times.
Tip 1 – Power supply unit
On no account must AS-Interface be grounded! Never use a normal power
supply unit only AS-Interface power supply units (PELV) with integrated data
de- coupling and connect “ground (GND)” with system ground.
Tip 2 – Network extention
Without repeaters or extenders the AS-Interface cable must be no longer
than 100 m – including all feeders to the assembly terminals! If you want to
expand the network please note the following:
Expansion with extenders:
• The maximum cable length between the extender and the master must be
no longer than 100 m
• Do not connect any slaves or AS-Interface network power supply unit
between the master and the extender.
• Lines “+” and “-” must not be swapped round.
Extension with repeaters:
• Up to two repeaters must be connected in series - that makes the cable
length in a feeder no more than 300 m (i.e. 3 segments with up to 100 m).
• An AS-Interface power supply unit must be connected at every repeater.
• An extender must not be connected beyond a repeater
Tip 4 – Additional auxillary power
If slaves are to be given an additional auxiliary power supply
• A PELV power supply unit and, if necessary, the black profiled auxiliary
power cable should be used.