Siemens TL.. Instruções de Operação Página 37

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 61
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 36
Application
3.15 Moving the cabinets
37
3.15.2 Lifting the SINVERT 350 and SINVERT 420 AC cabinet
If the AC cabinet is to be lifted with a crane, a special crane hook must be used, or the crane must be
mounted directly on the transformer.
The AC cabinet housing cannot support the weight of the transformer.
The special hook must be able to lift a weight of 1,800 kg. The fork of the hook must have the right length
(long enough to carry the transformer and short enough so that with the rear panel installed it does not
extend beyond the cabinet). In most cases, the lifting fork must be adjusted to the right length. Do not
remove the rear panel of the cabinet, because you cannot reattach the panel once the cabinet is installed
on-site (direct against the building wall).
Figure 3-23 Crane hooks
Forks completely inserted
underneath
Standard fork is too long
To use the crane hook, proceed as follows:
Remove the cabinet doors.
Place rubber mats between hook and transformer so that the cabinet cannot slip from the hook
(metal on metal does not provide sufficient grip).
Insert the hook directly beneath the transformer (to lift it).
Attach the cabinet top side to the hook using straps (to prevent tipping).
Vista de página 36
1 2 ... 32 33 34 35 36 37 38 39 40 41 42 ... 60 61

Comentários a estes Manuais