Technical Instructions POWERS™ Controls No. 4 Pneumatic Damper Actuator
Document Number 155-032P25
October 10, 2005
Page 10 Siemens Building Technologies, Inc.
Extended Shaft
Mounting - Fixed
Actuator,
Continued
4. Place the front of the actuator on the "X" dimension line so the actuator shaft faces
the damper shaft. Place the centerline of the actuator over the "Y" dimension line
(Figure 8).
5. Thread Clevis 331-801 onto the actuator shaft and tighten it against the lock nut.
Assemble Linkage Kit 331-958 (Table 6, Items 1 through 6) to the actuator assembly
per Figure 8. The linkage is assembled so the damper shaft will rotate CCW as
actuator pressure increases. This is a typical normally closed damper installation.
Figure 8. Fixed Mounted Actuator Assembly.
Dimensions in Inches (Millimeters).
Table 6. Linkage Kit 331-958 Parts
(Figure 8).
Item Part No. Description Qty. Material
1 331-918 Clevis pin 2 Zinc plated
steel
2 331-930 Spring washer 1 —
3 331-929 Washer 1 Nylon
4 331-941 Crank assembly 1 —
5 331-807 Hitch pin 2 Zinc plated
steel
6 331-922 4-inch link 1 Steel
Table 7. Linkage Kit 331-958 Crank Connections
(Figure 8).
Dimensions
Inches (Millimeters)
Application
Crank
Hole
Number
X Y
1 8-1/2
(216)
2
(51)
4-inch (102) stroke -
90° rotation
2 8-1/2
(216)
3
(76)
4-inch (102) stroke -
70° rotation
3 8
(203)
1-1/2
(38)
3-inch (76) stroke -
90° rotation
4 8
(203)
2-1/2
(64)
3-inch (76) stroke -
60° rotation