Technical Instructions POWERS™ Controls No. 3 Pneumatic Damper Actuator
Document Number 155-146P25
September 18, 2008
Page 4 Siemens Building Technologies, Inc.
Table 3. Thrust Torque Ratings.
Maximum Thrust lb. (N) Torque Rating* lb-in (Nm)
Full Stroke Forward 2-Position Operation
Nominal
Spring
Rang
e
15 psi
(103 kPa)
18 psi
(124 kPa)
25 psi
(172 kPa)
Spring
Return
(No Stroke)
0 psig
(0 kPa)
Gradual
Operation
15 psi
(103 kPa)
18 psi
(124 kPa)
25 psi
(172 kPa)
3 to 7 psi
(21 to 48 kPa)
64 (285) 88 (391) 144 (641) 24 (107) 10 (1.1) 20.2 (2.3) 20.2 (2.3) 20.2 (2.3)
5 to 10 psi
(35 to 69 kPa)
40 (178) 64 (285) 120 (534) 40 (178) 10 (1.1) 33.6 (3.8) 33.6 (3.8) 33.6 (3.8)
8 to 13 psi
(55 to 90 kPa)
16 (71) 40 (178) 96 (427) 64 (285) 10 (1.1) 53.8 (6.1) 53.8 (6.1) 53.8 (6.1)
* With maximum hysteresis of 2.5 psi (17.2 kPa) @ 90° rotation.
Sizing
The size and quantity of actuators required depends on several damper torque factors:
• Damper type (standard or low leakage)
• Quality of damper installation
• Number of damper sections
• Air velocity
• Static pressure
• Age of damper
To determine
the correct actuator req
uired for the installation:
• Obtain the damper torque ratings (lb-i
n/sq-ft) from the damper manufacturer.
• Determine the area of the damper.
• Calculate the total torque required to move the damper.
• Select the appropriate actuator(s).
Installation
Extended Shaft
Mounting, Pivot
Mounting
For Actuators 331-4311, 331-4511, 331-4811, or 332-4811. These assemblies are
designe
d for 90° damper rotation.
NOTE: Clevis mounts in Crank Radius Hole No. 6 for 90° damper rotation.
1.
Slip the 9/16-inch (14 mm) diameter hole in the mounting plate over
the damper
shaft (Figure 1).
2. Slip the crank over the 3/8 through 1/2-
inch (10 through 13-mm) diameter damper
shaft (Figure 2).
3. Position the mounting plate (Table 3).
4. Attach the mounting plate to the duct with four screws.