POWERS™ Controls No. 4 Pneumatic Damper Actuator Technical Instructions
Document Number 155-032P25
October 10, 2005
Siemens Building Technologies, Inc. Page 3
Specifications
Effective diaphragm area 11 inches
2
(71 cm
2
)
Stroke 4 inches (102 mm)
Stroke (Hesitation model) 3 inches (76 mm)
Stem Stainless steel
Housing Steel with cathodic epoxy electrocoat
Diaphragm Ozone-resistant, EPDM rubber
Bearing Oilite® sintered bronze bushing in
aluminum die casting
Maximum air pressure 30 psig (210 kPa)
Nominal spring ranges 3 to 7 psi (21 to 50 kPa)
3 to 13 psi (21 to 90 kPa)
5 to 10 psi (35 to 70 kPa)
8 to 13 psi (55 to 90 kPa)
Nominal spring range (Hesitation model) 2 to 3; 8 to 13 psi
(14 to 21; 55 to 90 kPa)
Ambient temperature range
Operating -20°F to 200°F (-29°C to 93°C)
Storage -20°F to 200°F (-29°C to 93°C)
Air connection elbow barb fitting for
1/4-inch OD plastic tubing Installed in 1/8-inch NPT opening
Type of mounting Front, bracket, pivot
Thrust and torque rating See Table 2
Dimensions See Figure 14
Agency Approvals Complies with UL555 and UL555S
Table 2. Thrust and Torque Rating.
Maximum Thrust lb (N) Torque Rating* lb-in (Nm)
Full Stroke Forward 2-position Operation or
with Positioner
Nominal
Spring
Range
15 psi
(103 kPa)
18 psi
(124 kPa)
25 psi
(172 kPa)
Spring Return
(No stroke)
0 psig (0 kPa)
Gradual
Operation
15 psi
(103 kPa)
18 psi
(124 kPa)
25 psi
(172 kPa)
3-7 psi
(21-50 kPa)
88 (391) 121 (538) 198 (881) 33 (147) 30 (3.4) 46 (5.2) 46 (5.2) 46 (5.2)
3-13 psi
(21-90 kPa)
22 (98) 55 (245) 132 (587) 33 (147) 30 (3.4) 30 (3.4) 46 (5.2) 46 (5.2)
5-10 psi
(35-70 kPa)
55 (245) 88 (391) 165 (734) 55 (245) 30 (3.4) 77 (8.7) 77 (8.7) 77 (8.7)
8-13 psi
(55- 90 kPa)
22 (98) 55 (245) 132 (587) 88 (391) 30 (3.4) 123 (14) 123 (14) 123 (14)
2-3, 8-13 psi
(14-21, 55-90 kPa)
Hesitation model
22 (98) 55 (245) 132 (587) 22 (98) 23 (2.6) — — —
* With maximum hysteresis of 2.5 psi (17.2 kPa) @ 90° rotation.