Siemens ITC Instruções de Operação Página 28

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 132
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 27
Installing and connecting the device
3.4 Connecting the device
Industrial Thin Client ITC1200, ITC1500, ITC1900, ITC2200
28 Operating Instructions, 04/2013, A5E03474888-02
Wiring diagram
Ground connection on the device, example
Equipotential bonding conductor cross-section: min. 4 mm
2
Control cabinet
Equipotential bonding conductor cross-section: min. 16 mm
2
Ground connection
Cable clip
Equipotential bonding rail
Parallel routing of the equipotential bonding conductor and data cable
NOTICE
Damage to the interface modules possible
Cable shielding is not suitable for equipotential bonding.
Use only the prescribed equipotential bonding conductors. The equipotential bonding
conductor
must not be less than 16 mm². The interface modules may otherwise be
damaged or destroyed.
Vista de página 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 ... 131 132

Comentários a estes Manuais

Sem comentários