Description of the DP Functions, Data, and Error Codes
DP Base Programming Interface for CP 5613/CP 5614
200
C79000-G8976-C108-01
Byte 9 (DPV1_Status_2)
Bit Meaning
7
Enable_Pull_Plug_Alarm
This bit is set to allow an alarm of the type "Pull_Plug_Alarm" to be
signaled.
6
Enable_Process_Alarm
This bit is set to allow an alarm of the type "Process_Alarm" to be
signaled.
5
Enable_Diagnostic_Alarm
This bit is set to allow an alarm of the type "Diagnostic_Alarm" to be
signaled.
4
Enable_Manufacturer_Specific_Alarm
This bit is set to allow all vendor-specific alarms to be signaled.
3
Enable_Status_Alarm
This bit is set to allow an alarm of the type "Status_Alarm" to be
signaled.
2
Enable_Update_Alarm
This bit is set to allow an alarm of the type "Update_Alarm" to be
signaled.
1 reserved
0
Check_Cfg_Mode
This bit can be used to influence the reaction to the reception of
configuration data. If the bit is set to 0, the check is as described in
EN 50170. If this bit is set, the check is made according to a specific
user definition.