Siemens SIMATIC NET PROFIBUS Manual de Serviço Página 196

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 238
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 195
Description of the DP Functions, Data, and Error Codes
DP Base Programming Interface for CP 5613/CP 5614
196
C79000-G8976-C108-01
Alarm_Mode
This parameter specifies the maximum number of possible active alarms.
Value Meaning
0 1 alarm of each alarm type
1 2 alarms in total
2 4 alarms in total
3 8 alarms in total
4 12 alarms in total
5 16 alarms in total
6 24 alarms in total
7 32 alarms in total
Add_Sl_Flag
Bit Name and Meaning
7-2 reserved
1
Ignore_AClr
0 means: execute AUTOCLEAR
1 means: ignore AUTOCLEAR
0
NA_To_Abort
0 means: the slave is not initialized if it does not respond.
1 means: the slave is reinitialized if it does not respond.