Appendix C: Device Data Format
70 Siemens Energy & Automation, Inc.
Alarm Function Status
Note: When bit numbers are
specified, Bit 15 is the
highest order bit in the
PLC register.
46 Bit Contents
15–10 Unused
9 Harmonic Distortion Alarm
8 Under PF Lag Alarm
7 Over PF Lead Alarm
6 Over kVAR Alarm
5 Over kVA Alarm
4 Over kW Demand Alarm
3Over kW Alarm
2Over Amp Demand Alarm
1 Grnd Over Amp Alarm
0 Over Amp Alarm
Protective Relay Status 47 Bit Contents
15–8 Unused
7 Under Frequency Alarm
6 Over Frequency Alarm
5 Over Reverse kW Alarm
4 Overvoltage Alarm
3 Voltage Unbalanced Alarm
2 Undervoltage Alarm
1 Current Unbalanced Alarm
0 Neutral Over Amp Alarm
Event Counter 48 0...65535
System Error Flag 49 0 = No System Errors
1 = EEPROM Write Error
2 = Status Update Error
3 = Clear Trip Log Error
4 = Trip Log Entry Error
5 = Breaker Test Error
6 = Trip Error
THD Phase A 50 0-100
THD Phase B 51 0-100
THD Phase C 52 0-100
THD Neutral 53 0-100
Device Command Data Retrieved From PLC (Energy/Comm)
First Command Word (Command Word) Second Command Word (Data or Value)
0 = No Command to Perform Unused for Command 0
1 = Reset All Demand Values Unused for Command 1
2 = Reset All Hour Counters Unused for Command 2
3 = Close Breaker Unused for Command 3
4 = Open Breaker Unused for Command 4
Real-Time Device Data Stored in PLC (Energy/Comm) (Continued)
Real-Time Data Register Location in
PLC Block
Range or Contents