8 DTU3005P Profibus Application Notes
46 Siemens Energy & Automation, Inc.
1. Two additional words precede the real-time
data, increasing the amount of data transferred
by two words. The first word contains the
Device Number (0-31) as configured on the
DTU3005P’s device list and the second word
will contain the device type code as follows:
1 = SAMMS LV
2 = SAMMS LV
3 = 4300 Power Meter
4 = 4700 Power Meter
5 = 4720 Power Meter
6 = Statis Trip III
7 = ISGS Switchgear
8 = S7 I/O
9 = SB EC
2. If the input configuration size is greater than the
number of words in the real-time data list for a
particular device, the unused input words at the
end of the data transferred is set to 0.
3. If the input configuration size is smaller than the
number of words in the real-time data list for a
particular device, the words at the end of the list
are not sent (they are truncated).
For examples of the real-time input data transferred
to the Profibus-DP host for SAMMS devices see
Section 8.7.
8.5 Example: Real-Time Data for
SAMMS MV Devices
For an Input Configuration Size of 20, see Tab le 8 . 3 .
For an Input Configuration Size of 16, see Ta b l e 8. 4 .
Note: The Control Parameters and Ambient
Temperature will not be sent because all
20 input words are already used. An input
configuration size of 24 Words is required
to receive all currently used data for the
SAMMS devices.
8.6 Profibus Output Data
Output data transferred from the Profibus host to
the DTU3005P is used to tell the DTU3005P to
issue commands to the devices. Examples of these
commands are Reset KWH Counters, Turn a Relay
On or Off, or Change a parameter value like the Tim-
ing Byte for the SAMMS device. Use of the output
data from the Profibus host to the DTU3005P is
optional. When output words are configured, exactly
four words will be transferred from the Profibus-DP
host to the DTU3005P. For the format of these
words, see Ta ble 8.5 .
Table 8.3 Input Configuration Size of 20
Word 0: Device Number (0-31)
Word 1: Device Type Code (2 = SAMMS MV)
Word 2: Motor Run Time (0-65535 hours)
Word 3: # of Motor Starts (0-65535 Starts)
Word 4: # of Trips (0-9999 Trips)
Word 5: Time to Restart (0-3245 seconds)
Word 6: Winding Temperature (0-250%)
Word 7: LED & Contactor Status
Word 8: Current Phase A (Low Order)
Word 9: Current Phase A (High Order)
Word 10: Current Phase B (Low Order)
Word 11: Current Phase B (High Order)
Word 12: Current Phase C (Low Order)
Word 13: Current Phase C (High Order)
Word 14: Current Ground (Low Order)
Word 15: Current Ground (High Order)
Word 16: Input/Pushbutton Status
Word 17: Timing Byte (0-200 seconds)
Word 18: Timing Byte 2 (0-200 seconds)
Word 19: Overload Trip Class (2-23)
Table 8.4 Input Configuration Size of 16
Word 0: Device Number (0-31)
Word 1: Device Type Code (2 = SAMMS MV)
Word 2: Motor Run Time (0-65535 hours)
Word 3: # of Motor Starts (0-65535 Starts)
Word 4: # of Trips (0-9999 Trips)
Word 5: Time to Restart (0-3245 seconds)
Word 6: Winding Temperature (0-250%)
Word 7: LED & Contactor Status
Word 8: Current Phase A (Low Order)
Word 9: Current Phase A (High Order)
Word 10: Current Phase B (Low Order)
Word 11: Current Phase B (High Order)
Word 12: Current Phase C (Low Order)
Word 13: Current Phase C (High Order)
Word 14: Current Ground (Low Order)
Word 15: Current Ground (High Order)
Table 8.5 Profibus-DP Word Format
Word 0: Device Number
0-31 as configured on the DTU3005P
Word 1: Device Type Code
See Section 8.4 - Profibus Input Data for list codes.
Table 8.3 Input Configuration Size of 20