Appendix A: Supported Devices
Siemens Energy & Automation, Inc. 51
A Supported Devices
The following Siemens ACCESS devices are sup-
ported by the DTU3005P.
In addition, the following Siemens protective relays
and measuring transducers using the VDEW proto-
col can be connected using the DTU3005P. This
device is designed for use with DIGSI Configuration
software. SEAbus port expander mode is not sup-
ported for this device.
A.1 Communication Port settings for
7-Series Protective Relays.
Following are the required settings in the relays for
communications.
All relays (except 7SJ600)
7SJ600
Table A.1 Supported Siemens Devices
Device
4720 Power Meter
4700 Power Meter
4300 Power Meter
Static Trip III Trip Unit
SAMMS-MV Motor Protection Device
SAMMS-LV Motor Protection Device
ISGS Intelligent SwitchGear System Protective Relay
S7-I/O Addressable Relay
Sentron SB Energy Communicating Trip Unit
StaticTrip III
SB-TL
Pulse Reading Meter (PRM)
Table A.2 Supported Siemens Protective Relays and
Measuring Transducers
Device
7SA511 Feeder Protection Relay
7SA513 EHV Line Protection Relay
7SD511 Current Comparison Protection Relay
7SD512 Current Comparison Protection Relay
7SJ511 Overcurrent Protection Relay
7SJ512 Feeder Protection Relay
7SJ531 Line and Motor Protection Relay
7SJ600 Overcurrent Protection Relay
7UT512 Differential Protection Relay
7UT513 Differential Protection Relay
7KG6000 (SIMEAS T) Measuring Transducer
Table A.3 7200 Rear port settings
Menu
Number
Menu Setting
7201 Device Address Set to a unique address to be
used in the DTU.
7208 Function Type This must be left at it's default
value of "176"
7221 Rear Port Parity Set this to 8N1, 8 data bits, no
parity, and 1 stop bit.
7222 Rear Format Set this to "VDEW Extension"
7225 Rear Baud Set this to match the baud rate of
the configuration in the DTU.
Table A.4 72 Port Settings
Menu Setting
DEVICE Set to a unique address, between 1 and
254, which will be used in the DTU
F-TYPE This should be left at it's default value of
"160"
PC-INT Data format of this interface should be
set to "DIGSI V3"
BAUD Set this to match the baud rate as config-
ured in the DTU
PARITY Set this to 8N1, 8 Data Bits, No Parity
Bits, and 1 stop bit