Building Technologies
Page 37 of 50 Last Revised: 4/11/2011
Parameter Parameter text Parameter Value Unit
Note: To change P0595 you first need to set P0010 = 5, and then set P0010 back to 0 afterwards.
p595 Selecting technological units [5] Pa
p596 Reference quantity, technological units 100
p753 CU analog inputs smoothing time constant
p753[0] AI0 (T. 3/4) 500 ms
p753[1] AI1 (T. 10/11) 500 ms
p753[2] AI2 (T. 50/51) 0 ms
p753[3] AI3 (T. 52/53) 0 ms
p756 CU analog inputs type
p756[0] AI0 (T. 3/4) [0] Unipolar voltage input (0 V ... +10 V)
p756[1] AI1 (T. 10/11) [0] Unipolar voltage input (0 V ... +10 V)
p756[2] AI2 (T. 50/51) [8] No sensor connected
p756[3] AI3 (T. 52/53) [8] No sensor connected
Note: The Ramp-up, Ramp-down, and Minimum Speed parameters are shown for the tuning process of the actual stair-press system, and may have to
be adjusted to suit.
p1080[0] Minimum speed 450 rpm
p1120[0] Ramp-function generator ramp-up time 30 s
p1121[0] Ramp-function generator ramp-down time 30 s
p1210 Automatic restart, mode
[26] Acknowledging all faults and reclosing for an ON
command
p2200[0] BI: Technology controller enable Control_Unit : r722.0
p2201[0] CO: Technology controller, fixed value 1 40 Pa
p2267 Technology controller upper limit actual value 120 Pa
p2268 Technology controller lower limit actual value -10 Pa
Note: The Prop gain and Integral time parameters are shown for the tuning process of the actual stair-press system, and may have to be adjusted to suit.
p2280 Technology controller proportional gain 1.2
p2285 Technology controller integral time 25 s
Note: Set the PID Loop minimum output value to match the minimum motor speed (P1080). For example; 30% for 15Hz (when the max speed is 50Hz).
p2292 CO: Technology controller minimum limiting 30 %
p2302 Technology controller output signal starting value 35 %
p3880 BI: ESM activation Control_Unit : r722.0
p3881 ESM setp source [4] Setpoint from technology controller
p3884 CI: ESM setpoint technology controller Control_Unit : p2201
p31020 Multi-zone control interconnection [1] Interconnecting multi-zone control
p31021 Multi-zone control configuration [0] Setpoint 1 / multiple actual values
p31022 Multi-zone control for actual value processing [10] Maximum (actual value 1, 2)
p31025 BI: Multi-zone control day/night switchover 0
p31026 CI: Multi-zone control actual-value input
p31026[0] CI: Multi-zone control actual-value input Control_Unit : r755[0]
p31026[1] CI: Multi-zone control actual-value input Control_Unit : r755[1]
p31026[2] CI: Multi-zone control actual-value input 0
p31023[0] CI: Multi-zone control setpoint input Control_Unit : p2201
Note: The following read-only parameters are shown as handy points of interest. Do not try to program these into your drive.
r755 CO: CU analog inputs actual value in percent
r755[0] CU analog inputs actual value in percent, AI0 (T. 3/4) 71.36 %
r755[1] CU analog inputs actual value in percent, AI1 (T. 10/11) 80.4 %
r755[2] CU analog inputs actual value in percent, AI2 (T. 50/51) 0 %
r755[3] CU analog inputs actual value in percent, AI3 (T. 52/53) 0 %
r2260
CO: Technology controller setpoint after ramp-function
generator
40 Pa
r2272 CO: Technology controller actual value scaled 80.41 Pa
r2294 CO: Technology controller output signal 0 %
r31027 CO: Multi-zone control actual-value output 80.41 %